Specification
Table
|
ST6K¡«ST60K£¨Three-
ins and Three out£©
|
|
Mode:
|
ST6K
|
ST10K
|
ST15K
|
ST20K
|
ST30K
|
ST40K
|
ST50K
|
ST60K
|
|
Capacity£¨KW£©
|
6KVA/4.8
|
10KVA/8
|
15KVA/12
|
20KVA/16
|
30KVA/24
|
40KVA/32
|
50KVA/40
|
60KVA/48
|
|
Battery
voltage
|
192V
|
336V
|
|
Overall
efficiency
|
¡Ý95%
|
|
Noise
|
¡Ü53dB£¨distance 1m£©
|
¡Ü56B£¨distance 1m£©
|
|
Size:
W¡ÁD¡ÁH(mm)
|
550¡Á600¡Á1135
|
650¡Á700¡Á1510
|
|
Weight(Kg)(excluding
the battery)
|
260
|
280
|
310
|
340
|
480
|
520
|
560
|
580
|
|
ST80K¡«400K£¨Three-
ins and Three out£©
|
|
Mode:
|
ST80K
|
ST100K
|
ST120K
|
ST150K
|
ST200K
|
ST250K
|
ST300K
|
ST400K
|
|
Capacity£¨KW£©
|
80KVA/64
|
100KVA/80
|
120KVA/96
|
150KVA/120
|
200KVA/160
|
250KVA/200
|
300KVA/240
|
400KVA/320
|
|
Battery
voltage
|
336V
|
|
Overall
efficiency
|
¡Ý95%
|
|
Noise
|
¡Ü60dB£¨distance 1m£©
|
¡Ü65B£¨£¨distance 1m£©
|
|
Size:
W¡ÁD¡ÁH(mm)
|
1250¡Á750¡Á1700
|
1450¡Á750¡Á1900
|
|
Weight£¨Kg£©(excluding
the battery)
|
780
|
860
|
980
|
1250
|
1600
|
1800
|
2100
|
2500
|
Common parameters
|
Input
|
Voltage
|
Three-phase four-wire
system, 380V¡À25%
|
|
Frequency
|
50Hz¡À10%
|
|
Power factor
|
¡Ý0.95
|
|
Output
|
Voltage
|
Three-phase four-wire
system, 380V¡À1%
|
|
Frequency
|
50Hz¡À0.05%(when power
is provided by battery)
|
|
Harmonic distortion
|
Pure sine wave, distortion
factor <3% (linear load), <5%( non-linear
load)
|
|
Unbalanced voltage
|
Balanced load¡Ü1%, unbalanced
load¡Ü3%
|
|
Phase displacement angle
|
Balanced load¡Ü1, unbalanced
load¡Ü3
|
|
Dynamic transient range
|
When output is 0¡«50%¡«100%¡Ü3%,
recovery time ¡Ü10ms
|
|
Overload capacity
|
125%¡Ý10min, 150%¡Ý20s
|
|
Peak factor
|
5:1
|
|
Switching time
|
Pure online zero switching
|
|
Battery
|
Type
|
Lead-acid sealed, maintenance-free
|
|
Charging method
|
PWM constant current
and constant voltage, battery intelligent
management system
|
|
Charging time (standard
type)
|
12 hours
|
|
System
performance
|
System performance MTBF
|
300,000 hours
|
|
Environment scope
|
temperature-10¡æ¡«50¡æ,
humidity 0¡«93% without condensation, altitude
¡Ü3000m
|
|
Support software interface
|
Novell Netware Microsoft
Windows9x Windows2000 Windows NT Linux
|
|
Other
|
Dustproof and moisture
proof, inverter isolating transformer,
thunderbolt surging wave absorption, and
manual bypass switch
|
|
|
Multiple
CPU Intelligent Control |
|
Battery
Switch-on Function |
| |
Advanced
multiple CPU intelligent control is one
digital software processed by microprocessor,
can precisely and integrally control UPS
data, and provide with enough calculation
capacity, so that UPS can be under the
best operation at any time.
|
|
The
device features its battery switch-on function,
at no public power supply for UPS device,
the battery can supply with power alternatively,
and then provide with stable AC power output,
thus more conveniently provide the customer
wit flexible solution for power supply. |
 |
Advance
IGBT inverted technology |
|
| |
Combined
advanced IGBT technology with hi-frequency
wider-modulated technology (PWM), the technology
can reduce systematic noise and power loss,
so that customer can obtain hi-quality power
output and optimized efficiency under each
operation load. |
 |
Advanced
control design structure |
| |
Advance
module design can reduce mean troubleshooting
time (MTTR) and keep up best service. and
best suitability for 100% 3-phase unbalanced
load and non-linear load, must not use the
UPS rated capacity under reduced capacity,
you can consistently operate under 3-phased
100% unbalanced load.
|
|
|
Intelligent
by-pass switch |
| |
UPS
can automatically monitor public power voltage
under by-pass circuit mode, if input voltage
exceeds rated value -20%¡«+50%, it shall
automatically terminate its voltage output
so as to protect from loaded equipment and
UPS itself. |
|
|
|
Personal
display interface |
| |
Intelligent
power management personal display panel
is made of mini LCD system, clearly provides
with integral operation status while UPS
operation, herein LCD shall display public
power, battery, output, load and interior
status information, thus greatly convenient
for operator and user. With remote monitor
of RS232 interface and self-test function
and timing switching function in this system,
the system can realize in monitoring and
alarming of each operation status, all information
above make it into real intelligent UPS. |
|
|
Advance
phase-balanced technology |
| |
With
most advanced phase-balanced technology
now, it features best stability, even
if loss-phase, it still operate at normal
condition, especially in some worse power
supply environment.
|
 |
Sole
parallel redundant structure
|
| |
Only
fully understandable for the key load of
power supply, you can design satisfactory
UPS system, the system adopts most advance
technology, featured as unique idea and
promoted for multiple UPS parallel structure
(RPA) so that system optimizes best reliability.
This series adopts parallel system to assure
each key part of UPS fully controlled, therefore,
the parallel redundancy is the best in the
property. |
|
|
|
|