Specification
Table(1/1、3/1)
|
DU2K~20K(Single
in and single out)
|
|
Mode:
|
DU2K
|
DU3K
|
DU6K
|
DU10K
|
DU15K
|
DU20K
|
|
Capacitg(KW)
|
20KVA/1.6
|
3KVA/2.4
|
6KVA/4.8
|
10KVA/8
|
15KVA/12
|
20KVA/16
|
|
Voltage
|
Single phase with two Lines+ground
wire ,220V±25%
|
|
Noise
|
≤52dB(distance 1m)
|
≤60dB(distance 1m)
|
|
Size:
(W×D×Hmm)
|
530×264×592
|
630×343×700
|
|
Weight(Kg)
(excludingthebattery)
|
65
|
70
|
80
|
145
|
160
|
180
|
|
DP6K~60K(Three-
ins and single out)
|
|
Mode:
|
DP6K
|
DP10K
|
DP15K
|
DP20K
|
DP30K
|
DP40K
|
DP50K
|
DP60K
|
|
Capacitg(KW)
|
6KVA/4.8
|
10KVA/8
|
15KVA/12
|
20KVA/16
|
30KVA/24
|
40KVA/32
|
50KVA/40
|
60KVA/48
|
|
Voltage
|
Three phase with four Lines+ground
wire,380V±25%
|
|
Noise
|
≤60dB(distance 1m)
|
≤65dB(distance 1m)
|
|
Size:
(W×D×Hmm)
|
620×343×995
|
650×700×1510
|
|
Weight(Kg)
(excludingthe battery)
|
130
|
165
|
180
|
220
|
400
|
450
|
530
|
620
|
Common
parameters(1/1、3/1)
|
Input
|
Frequency
|
50Hz/60Hz±10%
|
|
Power actor
|
≥92%
|
|
Output
|
Voltage
|
220V±0.5%
|
|
Voltage regulation
|
Stable voltage±1%,dynamic oltage±2%,(0-100%
load
fluctuation20ms)
|
|
Frequency stableness
|
50Hz/60Hz±0.5%
|
|
Frequency torsion
rate
|
Less than 1Hz / second
|
|
Instant load status
|
± 0.4%(100% instant load fluctuation)
|
|
Harmonic distortion
|
For linear load, less than 3%(full
load),total rectifying
harmonics is lass than 5%
|
|
Overload capacitance
|
150%
|
|
Wave form
|
Sine wave
|
|
|
Input AC to output
AC
|
Above 91%
|
|
Transfer
time
|
Mains power supply
fails or restores
|
0 second
|
|
Turns from UPS to
BYPASS
|
Less than 4 ms
|
|
Battery
|
DC Voltage
|
192V
|
|
Charging time
|
After it is fully charged,
it can be filled to 90% of the total
capacity after it is charged for 8 hours.
|
|
Warning
sound
|
Battery discharge
|
If the main power fails,
it buzzes once every 4 seconds.
|
|
If the battery is low, it buzzes once every 0.5 seconds.
|
|
If the battery stops
discharging, it buzzes continuously.
|
|
In fault tatus
|
Continuously buzzes
|
Internal
Protecting
device
LCD
panel
|
Battery
|
Automatically shuts down the machine
when the battery power is low, it has
no fuse switch protection.
|
|
Overload
|
After the overload (110~150%) lasts
for 30 seconds,it automatically jumps
to BYPASS. It can automatically restore
normal state.
|
|
Temperature is too
high
|
If the internal temperature of the
UPS>85°C, it will
automatically jump to BYPASS.
|
|
Output short circuit
|
Limits Current, automatically shuts
down the machine, without fuse switch
protection.
|
|
UPS is abnormal
|
Automatically jumps to BYPASS mode and starts direct mains power
supply.
|
|
Noise Filter
|
10~10KHz at 40 db;100KHz~100MHz
at 70db
|
|
LCD display
|
Indicating input and output voltage,
frequency; battery voltage and output
power (%).
|
|
Battery BVL
|
One LED, it glows when the battery voltage is low.
|
|
|
Temperature
|
0~40℃
|
|
Relative humidity
|
10%~90% (No condensation)
|
|
Operation condition
|
Lower than 1500 meters above sea
level (altitude)
|
Specification
Table(3/3)
|
DT6K~60K(Three-
ins and Three out)
|
|
Mode:
|
DT6K
|
DT10K
|
DT15K
|
DT20K
|
DT30K
|
DT40K
|
DT50K
|
DT60K
|
|
Capacity(KW)
|
6KVA/4.8
|
10KVA/8
|
15KVA/12
|
20KVA/16
|
30KVA/24
|
40KVA/32
|
50KVA/40
|
60KVA/48
|
|
Battery
voltage(V)
|
192V
|
|
Overall
efficiency
|
≥91%
|
|
Noise
|
≤53dB(distance
1m)
|
≤56B(distance
1m)
|
|
Size:
W×D×H(mm)
|
550×600×1135
|
650×700×1510
|
|
Weight(Kg)(excluding
the battery)
|
260
|
280
|
310
|
340
|
480
|
520
|
560
|
580
|
|
DT80K~400K(Three-
ins and Three out)
|
|
Mode:
|
DT80K
|
DT100K
|
DT120K
|
DT150K
|
DT200K
|
DT250K
|
DT300K
|
DT400K
|
|
Capacity(KW)
|
80KVA/64
|
100KVA/80
|
120KVA/96
|
150KVA/120
|
200KVA/160
|
250KVA/200
|
300KVA/240
|
400KVA/320
|
|
Battery
voltage(V)
|
240
|
384
|
|
Overall
efficiency
|
≥93%
|
≥94%
|
|
Noise
|
≤60dB(distance
1m)
|
≤65B((distance
1m)
|
|
Size:
W×D×H(mm)
|
1250×750×1600
|
1600×750×1600
|
|
Weight(Kg)(excluding
the battery)
|
780
|
860
|
980
|
1250
|
1600
|
1800
|
2100
|
2500
|
|
Input
|
Voltage
|
Three-phase
four-wire system,
380V±25%
|
|
Frequency
|
50Hz±10%
|
|
Power
factor
|
≥0.92
|
|
Output
|
Voltage
|
Three-phase
four-wire system,
380V±1%
|
|
Frequency
|
50Hz±0.05%(when
power is provided
by battery)
|
|
Harmonic
distortion
|
Pure
sine wave, distortion
factor <3% (linear
load), <5%( non-linear
load)
|
|
Unbalanced
voltage
|
Balanced
load≤1%, unbalanced
load≤3%
|
|
Phase
displacement angle
|
Balanced
load≤1, unbalanced
load≤3
|
|
Dynamic
transient range
|
When
output is 0~50%~100%≤3%,
recovery time ≤10ms
|
|
Overload
capacity
|
125%≥10min,
150%≥20s
|
|
Peak
factor
|
5:1
|
|
Switching
time
|
Pure
online zero switching
|
|
Battery
|
Battery
type
|
Lead-acid
sealed, maintenance-free
|
|
Charging
method
|
PWM
constant current and
constant voltage,
battery intelligent
management system
|
|
Charging
time (standard type)
|
12
hours
|
|
System
performance
|
System
performance MTBF
|
300,000
hours
|
|
Environment
scope
|
temperature-10℃~50℃,
humidity 0~93% without
condensation, altitude
≤3000m
|
|
Support
software interface
|
Novell
Netware Microsoft
Windows9x Windows2000
Windows NT Linux
|
|
Other
|
Dustproof
and moisture proof,
inverter isolating
transformer, thunderbolt
surging wave absorption,
and manual bypass
switch
|
|
|
Multiple
CPU Intelligent Control |
|
Battery
Switch-on Function |
|
|
Advanced
multiple CPU intelligent
control is one digital
software processed
by microprocessor,
can precisely and
integrally control
UPS data, and provide
with enough calculation
capacity, so that
UPS can be under the
best operation at
any time.
|
|
The
device features its
battery switch-on function,
at no public power supply
for UPS device, the
battery can supply with
power alternatively,
and then provide with
stable AC power output,
thus more conveniently
provide the customer
wit flexible solution
for power supply. |
 |
Advance
IGBT inverted technology |
|
| |
Combined
advanced IGBT technology
with hi-frequency wider-modulated
technology (PWM), the
technology can reduce
systematic noise and
power loss, so that
customer can obtain
hi-quality power output
and optimized efficiency
under each operation
load. |
 |
Advanced
control design structure |
|
|
Advance
module design can reduce
mean troubleshooting
time (MTTR) and keep
up best service. and
best suitability for
100% 3-phase unbalanced
load and non-linear
load, must not use the
UPS rated capacity under
reduced capacity, you
can consistently operate
under 3-phased 100%
unbalanced load.
|
|
|
Intelligent
by-pass switch |
|
|
UPS
can automatically monitor
public power voltage
under by-pass circuit
mode, if input voltage
exceeds rated value
-20%~+50%, it shall
automatically terminate
its voltage output so
as to protect from loaded
equipment and UPS itself. |
|
|
|
Personal
display interface |
|
|
Intelligent
power management personal
display panel is made
of mini LCD system,
clearly provides with
integral operation status
while UPS operation,
herein LCD shall display
public power, battery,
output, load and interior
status information,
thus greatly convenient
for operator and user.
With remote monitor
of RS232 interface and
self-test function and
timing switching function
in this system, the
system can realize in
monitoring and alarming
of each operation status,
all information above
make it into real intelligent
UPS. |
|
|
Advance
phase-balanced technology |
|
|
With
most advanced phase-balanced
technology now, it
features best stability,
even if loss-phase,
it still operate at
normal condition,
especially in some
worse power supply
environment.
|
 |
Sole
parallel redundant
structure
|
| |
Only
fully understandable
for the key load of
power supply, you can
design satisfactory
UPS system, the system
adopts most advance
technology, featured
as unique idea and promoted
for multiple UPS parallel
structure (RPA) so that
system optimizes best
reliability. This series
adopts parallel system
to assure each key part
of UPS fully controlled,
therefore, the parallel
redundancy is the best
in the property. |
|
|